1Fuel Log is the latest addition to FloScan's fuel flow line of digital instruments for diesel engines rated from 30 - 5000 kW.
In areas where EPA air quality regulations apply, Fuel Log addresses the need for accurate flow measurement to determine baselines for NOx emission reporting.
Fuel Log can also point out poor engine performance (poor injection, failed turbo's, etc...) as well as possible fuel theft. Discrepancies between tank fill-up records and the totalizer reading will identify this problem immediately.
Fuel Log can also be used for fuel billing purposes by monitoring precise fuel consumption per job or contract.
Fuel Log Model Features:
- Instantaneous net fuel burn rate.
- Cumulative (non-resettable) fuel totalizer.
- Resettable fuel (job) totalizer.
- Resettable engine (job) hour meter.
- Pulse signal output for instantaneous net fuel usage. Can be interfaced with Data Logger or Acquisition System for recording fuel usage.
- (+/-) 2% accuracy with retro-calibration on generator applications.
- Models available in U.S. gallons or liters.
- Operates on 12VDC. 32V/24V voltage reducer available upon request.
Uses include:
- Provides accurate fuel usage data for NOx emission reporting.
- Identifies poor engine performance with increases in normal fuel consumption.
- Possible fuel theft can be identified immediately by comparing fill-up records with totalizer reading.
- Provides accurate fuel usage data for billing purposes.
- Cumulative fuel totalizer can be used for determining engine service intervals.
- Pinpoints optimal engine speed under any load or operating condition.
Principal of Operation:
Most diesel engine fuel systems employ forward and return fuel flow lines. The return flow amount must be measured and subtracted from the forward flow amount to determine consumption. Inaccuracies in flow measurement in either direction can compound the amount of error in measurement. The amount of return flow varies by engine type - from as little as 10% of fuel consumption to a much as 1000% or more... necessitating very tight margins for error when measuring flows and calculating the difference. With regard to engines that use the return flow to cool unit injectors (e.g., CAT 3500/3600 Series, Detroit/MTU, and Cummins QS Series), the return flow temperature is substantially higher than the forward flow - leading to the possibility of error in measurement caused by the expansion of fuel. FloScan has designed special temperature compensated systems to accurately measure and compensate for these inconsistencies. Each pair of FloScan sensors (forward and return) is individually calibrated and matched to the microprocessor-driven meterhead.
 |
Series 7500/7600 Multifunction Meter (U.S.) |
Our Series 7500/7600 Multifunction Meter combines a digital LCD Engine Hour Meter, Tachometer, Fuel Flowmeter, and Fuel Totalizer in a single 3-3/8" diameter instrument which fits the panel space of a standard tach. A popular option is to replace the existing tach(s) with this system thus eliminating the need to cut new holes in the panel. |
» Read More |
|
 |
Series 75000/76000 Multifunction Meter (metric) |
A Series 75000/76000 Multifunction Fuel Monitoring System combines a digital LCD Engine Hour Meter, Tachometer, Fuel Flowmeter, and Fuel Totalizer in a single 86mm diameter instrument which fits the panel space of a standard tachometer. Perfect for determining the most efficient engine speed and the exact amount of fuel in your tanks. Models are available for virtually all diesel engines from 25 hp to 6000 hp. |
» Read More |
|
 |
Series 8500/8600 Fuel Flow Interface System (U.S.) |
A Series 8500/8600 Fuel Flow Interface System combines a digital LCD Engine Hour Meter, Tachometer, Fuel Flowmeter, and Fuel Totalizer in a single 3-3/8" diameter instrument which fits the panel space of a standard tachometer. This meter also provides a fuel flow rate output signal for GPS systems, data acquisition systems, and for FloScan Series 9700/9800 GPS Interface systems in twin diesel engine boats. |
» Read More |
|
 |
Series 85000/86000 Fuel Flow Interface System (metric) |
A Series 85000/86000 Fuel Flow Interface System combines a digital LCD Engine Hour Meter, Tachometer, Fuel Flowmeter, and Fuel Totalizer in a single 3-3/8" diameter instrument which fits the panel space of a standard tachometer. This meter also provides a fuel flow rate output signal for GPS systems, data acquisition systems, and for FloScan Series 97000/98000 GPS Interface systems in twin diesel engine boats. |
» Read More |
|
|